NUT
Do you have a UPS? Do you want to have you system gracefully shutdown in case of a power outage? This guide will show how you can make the most out of your UPS by using NUT from the Network UPS Tools project
Installation
USE flag
If you are connecting your UPS via USB, make sure to set the usb
USE flag:
USE flags for sys-power/nut Network-UPS Tools
+man
|
Build and install man pages |
+usb
|
Includes all UPS drivers that use USB. |
cgi
|
Add CGI script support |
doc
|
Add extra documentation (API, Javadoc, etc). It is recommended to enable per package instead of globally |
gpio
|
Includes all UPS drivers that use GPIO. |
i2c
|
Includes all UPS drivers that use I2C. |
ipmi
|
Includes all UPS drivers that use ipmi. |
modbus
|
Includes all UPS drivers that use MODBUS. |
monitor
|
Add a QT5 gui monitor. |
python
|
Add optional support/bindings for the Python language |
selinux
|
!!internal use only!! Security Enhanced Linux support, this must be set by the selinux profile or breakage will occur |
serial
|
Includes all UPS drivers that use SERIAL. |
snmp
|
Includes all UPS drivers that use SNMP. |
ssl
|
Add support for SSL/TLS connections (Secure Socket Layer / Transport Layer Security) |
systemd
|
Enable use of systemd-specific libraries and features like socket activation or session tracking |
tcpd
|
Add support for TCP wrappers |
test
|
Enable dependencies and/or preparations necessary to run tests (usually controlled by FEATURES=test but can be toggled independently) |
xml
|
Includes all UPS drivers that use XML. |
zeroconf
|
Support for DNS Service Discovery (DNS-SD) |
Emerge
root #
emerge --ask sys-power/nut
Configuration standalone
Search a UPS with nut-scanner:
root #
/usr/bin/nut-scanner
Scanning USB bus. Scanning XML/HTTP bus. No start IP, skipping NUT bus (old connect method) [nutdev1] driver = "usbhid-ups" port = "auto" vendorid = "051D" productid = "0002" product = "Back-UPS SMC 1500 FW:879.L4 .I USB FW:L4" serial = "***" vendor = "American Power Conversion" bus = "003"
Take note of driver name and port type for configuration file.
If UPS is connected via USB port, add user nut to group usb.
root #
usermod -a -G usb nut
Files
/etc/nut/nut.conf
Set mode to standalone if your machine is connected to the UPS directly and you want to run NUT on this machine.
root #
nano -w /etc/nut/nut.conf
/etc/nut/nut.conf
Desired settingsMODE=standalone
/etc/nut/ups.conf
This is where you set up your UPS configuration. Make sure that your UPS name (the text in the brackets) doesn't have any spaces. For configuration specific to your UPS you need to look it up here: NUT Hardware Compatibility Lookup
root #
nano -w /etc/nut/ups.conf
/etc/nut/ups.conf
Example ups.conf configuration[APCSMC1500] driver = usbhid-ups port = auto desc = "APC SMC1500 UPS" # Change some variables in UPS hardware. Not all devices or drivers # implement this, so this may not have effect on your system. override.battery.charge.low = 30 override.battery.runtime.low = 180
/etc/nut/upsd.users
You need to configure at least one user so that upsmon can be launched later. upsd will create a TCP connection that upsmon will use to check on the status of your UPS.
root #
nano -w /etc/nut/upsd.users
/etc/nut/upsd.users
Example upsd.users configuration[monmaster] password = mypassword upsmon master
/etc/nut/upsmon.conf
Create a MONITOR configuration in /etc/nut/upsmon.conf:
root #
nano -w /etc/nut/upsmon.conf
/etc/nut/upsmon.conf
Example upsmon configurationMONITOR APCSMC1500@127.0.0.1 1 monmaster mypassword master # If you want that NUT can shutdown the computer, you need root privileges: RUN_AS_USER root MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h +0" NOTIFYCMD /usr/sbin/upssched POLLFREQ 5 POLLFREQALERT 1 HOSTSYNC 15 DEADTIME 15 POWERDOWNFLAG /etc/killpower NOTIFYMSG ONLINE "UPS %s on line power" NOTIFYMSG ONBATT "UPS %s on battery" NOTIFYMSG LOWBATT "UPS %s battery is low" NOTIFYMSG FSD "UPS %s: forced shutdown in progress" NOTIFYMSG COMMOK "Communications with UPS %s established" NOTIFYMSG COMMBAD "Communications with UPS %s lost" NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding" NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced" NOTIFYMSG NOCOMM "UPS %s is unavailable" NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible" NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC NOTIFYFLAG LOWBATT SYSLOG+WALL NOTIFYFLAG FSD SYSLOG+WALL+EXEC NOTIFYFLAG COMMOK SYSLOG+WALL+EXEC NOTIFYFLAG COMMBAD SYSLOG+WALL+EXEC NOTIFYFLAG SHUTDOWN SYSLOG+WALL+EXEC NOTIFYFLAG REPLBATT SYSLOG+WALL+EXEC NOTIFYFLAG NOCOMM SYSLOG+WALL+EXEC NOTIFYFLAG NOPARENT SYSLOG+WALL RBWARNTIME 43200 NOCOMMWARNTIME 600 FINALDELAY 5
/etc/nut/upssched.conf
You need to configure operations on that upsmon will check on the status of your UPS.
root #
nano -w /etc/nut/upssched.conf
/etc/nut/upssched.conf
Example upssched.conf configurationCMDSCRIPT /usr/bin/upssched-cmd PIPEFN /var/lib/nut/upssched/upssched.pipe LOCKFN /var/lib/nut/upssched/upssched.lock AT ONBATT * START-TIMER onbatt 300 AT ONLINE * CANCEL-TIMER onbatt online AT LOWBATT * EXECUTE onbatt AT COMMBAD * START-TIMER commbad 30 AT COMMOK * CANCEL-TIMER commbad commok AT NOCOMM * EXECUTE commbad AT SHUTDOWN * EXECUTE powerdown AT REPLBATT * EXECUTE replacebatt
root #
mkdir -p /var/lib/nut/upssched
root #
chown nut:nut /var/lib/nut/upssched
/usr/bin/upssched-cmd
root #
nano -w /usr/bin/upssched-cmd
/usr/bin/upssched-cmd
Example upssched.conf configuration#! /bin/sh # # This script should be called by upssched via the CMDSCRIPT directive. # # Here is a quick example to show how to handle a bunch of possible # timer names with the help of the case structure. # # This script may be replaced with another program without harm. # # The first argument passed to your CMDSCRIPT is the name of the timer # from your AT lines. case $1 in onbatt) logger -t upssched-cmd "The UPS is on battery" mail -s "The UPS is on battery" admin@example.com # For example, uncommenting, you can stop some power-hog services #rc-service boinc stop #rc-service xmr-stak stop ;; online) logger -t upssched-cmd "The UPS is back on power" mail -s "The UPS is back on power" admin@example.com # For example, uncommenting, you can restart useful power-hog services #rc-service boinc start #rc-service xmr-stak start ;; commbad) logger -t upssched-cmd "The server lost communication with UPS" mail -s "The server lost communication with UPS" admin@example.com ;; commok) logger -t upssched-cmd "The server re-establish communication with UPS" mail -s "The server re-establish communication with UPS" admin@example.com ;; powerdown) logger -t upssched-cmd "The UPS is shutting down the system" mail -s "The UPS is shutting down the system" admin@example.com ;; replacebatt) logger -t upssched-cmd "The UPS needs new battery" mail -s "The UPS needs new battery" admin@example.com ;; *) logger -t upssched-cmd "Unrecognized command: $1" ;; esac
Services
OpenRC
To add the services to start on system boot:
root #
rc-update add upsdrv default
root #
rc-update add upsd default
root #
rc-update add upsmon default
To start upsd now run:
root #
rc-service upsdrv start
root #
rc-service upsd start
root #
rc-service upsmon start
Check the status of your ups manually. Note that you might have to adjust your UPS name for this work.
root #
upsc APCSMC1500@127.0.0.1 ups.status
OL
OL means that your UPS is "online" and not drawing from the battery. It also means that you configured the above files correctly.
If you want nut to power off your UPS when it shuts down your system in a power failure, you must add nut.powerfail to your shutdown runlevel:
root #
rc-update add nut.powerfail shutdown
LAN client/server configuration
Server configuration
Starting from standalone configuration, change:
Server files
/etc/nut/nut.conf
root #
nano -w /etc/nut/nut.conf
/etc/nut/nut.conf
Desired settingsMODE=netserver
/etc/nut/upsd.conf
root #
nano -w /etc/nut/upsd.conf
/etc/nut/upsd.conf
Desired settingsLISTEN 127.0.0.1 3493 LISTEN 192.168.1.1 3493
/etc/nut/upsd.users
root #
nano -w /etc/nut/upsd.users
/etc/nut/upsd.users
Example upsd.users configuration[monmaster] password = mypassword upsmon master [monslave] password = mypassword upsmon slave
Client files
/etc/nut/nut.conf
root #
nano -w /etc/nut/nut.conf
/etc/nut/nut.conf
Desired settingsMODE=netclient
/etc/nut/ups.conf
This file is not needed for slave monitor, so you can leave blank or full of comments.
/etc/nut/upsd.conf
This file is not needed for slave monitor, so you can leave blank or full of comments.
/etc/nut/upsd.users
root #
nano -w /etc/nut/upsd.users
/etc/nut/upsd.users
Example upsd.users configuration[monslave] password = mypassword upsmon slave
/etc/nut/upsmon.conf
Create a MONITOR configuration in /etc/nut/upsmon.conf:
root #
nano -w /etc/nut/upsmon.conf
/etc/nut/upsmon.conf
Example upsmon configurationMONITOR APCSMC1500@192.168.1.1 1 monslave mypassword slave
/etc/nut/upssched.conf
This file can be the same of standalone configuration.
/usr/bin/upssched-cmd
This file can be the same of standalone configuration.
Client services
On client machine, you need only upsmon service. To add the services to start on system boot:
root #
rc-update add upsmon default
To start upsd now run:
root #
rc-service upsmon start
Check the status of your ups manually. Note that you might have to adjust your UPS name for this work.
root #
upsc APCSMC1500@192.168.1.1 ups.status
OL